The Process Database

The process database is EPICS’s central idea and the part that takes longest to internalise. It is a declarative, continuously evaluated dataflow graph that happens to be written in a syntax resembling a config file.

Authoritative references:

Anatomy of a record

record(ai, "SR-C05-VA-IP-03:Pressure") {
    field(DESC, "Sector 5 ion pump 3 pressure")
    field(DTYP, "stream")
    field(INP,  "@ionpump.proto getPressure($(PORT))")
    field(SCAN, "1 second")
    field(EGU,  "mbar")
    field(PREC, "3")
    field(LINR, "NO CONVERSION")
    field(HIGH, "1e-8")   field(HSV,  "MINOR")
    field(HIHI, "1e-7")   field(HHSV, "MAJOR")
    field(ADEL, "5")      # archive deadband: log if changed by >5%
    field(MDEL, "1")      # monitor deadband: notify if changed by >1%
    field(TSE,  "0")      # timestamp source: 0 = IOC clock at processing
}

record(<type>, "<name>") then fields. That’s the whole syntax. The subtlety is entirely in which fields exist and what they do.

Fields every record has

Field Purpose
VAL The value. PVname alone means PVname.VAL.
NAME, DESC Name and a 40-character description. DESC shows up on screens and in the alarm tree, so writing it well is real work.
SCAN When this record processes.
DTYP Which device support to use. Soft Channel means “no hardware, get the value from a link”.
PHAS Ordering within a scan pass — lower phases process first. The tool for “read all inputs before computing”.
PINI Process once at iocInit. Essential for output records that must push an initial value.
SEVR, STAT Current alarm severity and status. Read-only.
TIME, TSE, TSEL The timestamp, and where it comes from — the IOC clock, a hardware event, or another record.
DISA, DISV, SDIS Conditional disabling. SDIS supplies a value; if it equals DISV, the record does not process.
ASG Access security group.
FLNK Forward link: process this record next, after I’m done.

Analog-record fields you’ll set constantly

Field Purpose
EGU Units string. Every screen displays it. Fill it in.
PREC Display precision.
LOPR, HOPR Display range — what a bar graph or dial scales to.
DRVL, DRVH Drive limits on output records: writes are clamped to this range by the IOC. A cheap, local, always-enforced protection that no client can bypass.
LOLO/LOW/HIGH/HIHI + LLSV/LSV/HSV/HHSV Alarm limits and the severity each raises.
HYST Alarm hysteresis — the cure for a value chattering across a limit.
MDEL Monitor deadband. Change smaller than this posts no monitor. Directly controls network load.
ADEL Archive deadband. Change smaller than this posts no archive event. Directly controls storage cost.
SMOO First-order smoothing filter, 0–1. Convenient and occasionally a trap: you are now archiving a filtered value and calling it a measurement.
LINR, EGUL, EGUF, ESLO, EOFF Raw-to-engineering conversion. Linear, or one of the built-in breakpoint tables for thermocouples and RTDs.

!!! tip “MDEL and ADEL are the two most consequential fields nobody sets” A noisy analog input with MDEL unset posts a monitor on every process, to every client, forever. Multiply by 400 000 records and you have designed a network problem. Setting these thoughtfully at record-creation time is much easier than retrofitting them across a facility.

Record types worth knowing

Grouped by what they’re for. Full list in the record types reference.

Input: ai (analog), bi (binary), mbbi (enumerated), mbbiDirect (bit field → 16 bits), longin, int64in, stringin, lsi (long string), waveform (arrays), aai.

Output: ao, bo, mbbo, mbboDirect, longout, int64out, stringout, lso, aao.

Computation and logic:

Type What it does
calc Evaluates CALC expression over inputs INPAINPL. The workhorse.
calcout calc plus an output link, optional delay (ODLY), and output-execution conditions (OOPT) — “write only when the result changes”, “only on transition to non-zero”.
acalcout Array version.
seq Writes up to sixteen values to sixteen links, optionally with delays. Sequencing without a state machine.
sub, aSub Calls a C function you’ve registered. The escape hatch when expressions run out.
fanout Processes up to sixteen records in order.
dfanout Distributes one value to up to eight outputs.
sel Selects one of several inputs — specific index, max, min.
compress Array compression: circular buffer, N-to-1 averaging, min/max. How you build a local history buffer.
histogram Accumulates a value into bins.
state, permissive Small stateful helpers, occasionally exactly right.

From modules: motor (motor), scaler, transform and swait (calc), sscan (sscan), busy (busy), asyn (asyn), NDPluginBase-driven records (areaDetector).

A link is a field whose value is a reference, not data. Three kinds:

Kind Example Meaning
Constant field(INPA, "3.14") A literal, applied at init.
Database (DB) link field(INPA, "OtherRecord.VAL PP") A record in this IOC. Resolved at init; direct memory access, no network, and the source of lock sets.
Channel Access (CA) link field(INPA, "OtherIoc:Record CP") Goes over the network, even to a record in the same IOC if you force it with CA.
Modifier Effect
NPP No Process Passive: read the target’s current value without processing it. Default. Fast; may be stale.
PP Process Passive: process the target first (if it’s Passive), then read it. Gets you a fresh value.
CA Force the link through Channel Access even for a local record — breaks the lock set deliberately.
CP CA + Process: monitor the target; process this record whenever the target changes. Event-driven, no polling.
CPP Like CP but only processes this record if it is Passive.
MS / MSS / MSI / NMS Maximise Severity: propagate the target’s alarm severity (all / status too / only INVALID / not at all). This is how alarms flow through a database.

Two idioms cover most real work:

# 1. Pull-on-demand: a summary computed only when someone reads it
record(calc, "Sys:TotalPower") {
    field(SCAN, "Passive")
    field(INPA, "PS1:Power PP MS")   # process each source, inherit its severity
    field(INPB, "PS2:Power PP MS")
    field(CALC, "A+B")
}

# 2. Push-on-change: react immediately, no polling anywhere
record(calc, "Sys:Interlock") {
    field(INPA, "Vac:Pressure CP MS")  # any change to either input...
    field(INPB, "Temp:Reading CP MS")  # ...processes this record
    field(CALC, "(A<1e-7)&&(B<40)")
    field(OUT,  "Perm:Beam PP")
}

Prefer CP over periodic scanning wherever the semantics allow: fewer wasted cycles, lower latency, and the resulting behaviour is easier to reason about.

Scanning and processing

SCAN When it processes
Passive Only when asked — a PP link, an FLNK, or a client write. The default and the most common.
Event On event number EVNT. Post events from software (post_event) or a timing system. The tool for machine-synchronous acquisition.
I/O Intr When the driver says there’s new data. Lowest latency, least waste — use it whenever support offers it.
10 second.1 second The ten standard periodic rates. Configurable in dbd if you need others.

Scan tasks and priority. Each periodic rate runs on its own thread; records also carry PRIO (LOW/MEDIUM/HIGH) which selects the callback queue for processing triggered asynchronously. A slow device on the wrong priority can starve the queue it shares.

Synchronous vs asynchronous processing. Device support that can’t answer immediately (a 200 ms serial round trip) marks the record PACT (processing active), returns, and completes later via a callback. The scan thread isn’t blocked — but a second process request while PACT is set is discarded, which is why hammering a slow record with caput silently loses writes. This is also why the busy record exists: to represent “still working” to clients honestly.

Lock sets: the thing that eventually bites you

Records connected by DB links (not CA links) form a lock set. Before processing any record in a lock set, the IOC takes a single lock covering the whole set.

Consequences:

dbLockShowLocked on the IOC shell shows lock sets. If a database “feels slow” for no visible reason, look here.

Templates and substitutions

You do not write 176 BPMs by hand.

# bpm.template
record(ai, "$(P)$(R):X") {
    field(DESC, "$(DESC=Horizontal position)")
    field(INP,  "@$(PORT) X $(ADDR)")
    field(EGU,  "mm")
    field(PREC, "4")
    field(HIHI, "$(XLIMIT=2.0)")  field(HHSV, "MAJOR")
}
record(ai, "$(P)$(R):Y") {
    field(INP,  "@$(PORT) Y $(ADDR)")
    field(EGU,  "mm")
    field(PREC, "4")
}
# bpms.substitutions
file "bpm.template" {
    pattern { P,          R,        PORT,    ADDR, XLIMIT }
            { "SR-C01-", "DI-BPM-01", "BPM1", 0,    2.0 }
            { "SR-C01-", "DI-BPM-02", "BPM1", 1,    2.0 }
            { "SR-C02-", "DI-BPM-01", "BPM2", 0,    1.5 }
}

msi (macro substitution and include) expands these at build time; dbLoadTemplate can expand at load time. Notes from experience:

Database design guidance

Accumulated wisdom, mostly learned the hard way by other people:

Do the work in the database, not in a client. Logic in a calc record runs at IOC priority, survives network partitions, is visible to dbpr, and keeps working when the operator’s laptop closes. The same logic in a Python script is invisible, unmonitored, and stops when someone reboots a workstation. If a client script is holding your machine in a state, that logic is in the wrong place.

Put alarm limits on the record, not on the screen. Screen-side thresholds are invisible to the alarm system, the archiver, and everyone not looking at that screen.

Use DRVL/DRVH on every output record. Free, local, unbypassable clamping. Set them the day you create the record.

Name the record for what it is, not where it’s wired. ...:Current-RB outlives three generations of ADC channel assignment.

Distinguish setpoint from readback in the name. The -SP / -RB (or :Set / :Get) convention exists because confusing “what I asked for” with “what it’s doing” is a genuinely dangerous class of mistake. See naming conventions.

Set MDEL and ADEL on anything noisy. Before it’s deployed, not after the network team calls.

Don’t build big cross-IOC link webs. CA links between IOCs are fine in small numbers and become an unmaintainable, order-dependent tangle in large ones. Where subsystems must interlock, prefer one IOC that owns the decision, or push it to hardware.

Keep PINI in mind for output records. Without it, an output record’s value on a fresh boot is whatever VAL defaulted to, and it will not be pushed to hardware until something processes it. With autosave, it’s restored — which is why autosave and PINI are usually discussed together.

Tools for working on databases

Tool Use
dbl / dbgrep List records in a running IOC, optionally by pattern.
dbpr <record> <level> Print all fields of a record. Levels 0–4 for increasing detail. Your primary debugging tool.
dbtr <record> Test-process a record and print the result.
dbLockShowLocked Show lock sets.
dbdr / dbior Report DBD contents / driver state.
VDCT Graphical .db editor showing links as a wiring diagram. Legacy Java, still genuinely useful for reading someone else’s database.
ibek Generates databases and startup scripts from YAML device descriptions.
dbVerify / dbLoadRecords at build time Catch syntax errors before deployment rather than at 2 a.m.

Next

Protocols — how those records get onto the network.